Typical electricity unit prices are:
A figure of 0.537 Kg per kWh for CO2 generation is provided by the Carbon Trust.
| Nominal | Lamp | Actual |
| 28 W | 1200mm T5 | 30 W |
| 54 W | 1200mm T5 | 58 W |
| 35 W | 1500mm T5 | 38 W |
| 49 W | 1500mm T5 | 53 W |
| 80 W | 1500mm T5 | 83 W |
| 36 W | 1200mm T8 | 41-45W |
| 58 W | 1500mm T8 | 64-70W |
| 70 W | 1800mm T8 | 77-83W |
| 100 W | 2400mmT12 | 122 W |
| 55 W | TC-L | 56 W |
| 80 W | TC-L | 83 W |
| 250 W* | SON* | 275 W* |
| 400 W* | SON* | 435 W* |
| 250 W* | M-Halide* | 275 W* |
| 400 W* | M-Halide* | 430 W* |
| 400 W* | Mercury* | 425 W* |
High pressure discharge lamps are not suitable for dimming or switching with presence detection
| % Light Output | % Power Usage |
| 100 | 100 |
| 90 | 90 |
| 80 | 81 |
| 70 | 73 |
| 60 | 66 |
| 50 | 59 |
| 40 | 51 |
| 30 | 42 |
| 20 | 33 |
| 10 | 21 |
| 3 | 14 |
| 1 | 13 |
| 0 | 0 |